Cold air leaking through doors and joints fools the O₂ probe: the trim cuts burner air, the flame goes rich and fuel use rises.

Simulator developed by José Geraldo da Silva Moreira · Energy-efficiency lab

The analyzer says there is excess air. The flame says there isn't.

Cold air enters through doors, sight glasses and joints downstream of the burners and reaches the O₂ probe at the furnace exit.

O₂ trim
O₂ measured by the probe
what the control “sees”
Actual λ at the burners
Overall λ
burners + infiltration
Extra fuel
vs. a tight furnace at the same O₂

Furnace, side view

What to watch
  • With trim on and 20% false air, the control cuts burner air until measured O₂ meets the setpoint. The flame goes sub-stoichiometric.
  • A double penalty: false air enters cold (it bypasses the recuperator) and the rich flame leaves CO in the furnace atmosphere.
  • The fix: slightly positive furnace pressure control, sealing, and CO measured alongside O₂.
Assumes false air mixes with the flue gas before the probe and that the CO formed does not fully burn before measurement.

Simplified teaching models with order-of-magnitude illustrative values. Do not use them for design or operating decisions without validation against plant data.